battery-informer-graphic-transparent

PRODUCT FEATURES & INFORMATION

  • Tells if the battery is “Good”, “Warning” or “Failed”
  • IEEE approved Ohmic reading
  • Non-Invasive
  • Highly reliable
  • Self learning baseline
  • Resettable for new batteries
  • 1-2 Year ROI
  • For use with VRLA, Gel, AGM batteries
  • Dimensions: 55mm x 55mm x 19mm (sensor)
  • Power consumption
  • No internal battery
  • Operating temp-15C to 85C
  • Display LCD – Digital, graphical, icons
  • Reverse wiring protection

METHOD OF PROCEDURE (MOP)

MPI NARADA PRODUCT LITERATURE

MPI NARADA PRODUCT SPECIFICATIONS

BATTERY STATE OF HEALTH INDICATOR

Description Battery Failure Warning System for VRLA Batteries
Part Number BI-12V-Smart-100
Applications VRLA batteries for use in backup-power systems: UPS, telecom, renewable energy, industrial applications

Operating Parameters

System voltage, nominal 12V
Input voltage range 9 – 16V DC
Battery constructions supported Rechargeable VRLA, SLA, AGM
Battery types supported High rate, long life, general purpose batteries
Power consumption <4mAh (sensor)
Internal battery None
Operating temp -15C to 85C*
Battery size range 28 to 200 AH at the 8 hour rate
Battery connection 8mm ‘Y’ for auto terminal
Display LCD – Digital, graphical, icons
Buttons None
Test frequency Every minute
Test time ~0.03 sec.
Test technology Ohmic
Warranty 1 year
Reverse wiring protection Yes

Performance and Diagnostics

Replace battery indicator Yes
Automatic battery baseline developer and calibration Yes
State of Health (SOH) health test Yes
State of Health (SOH) health analysis Yes
Manual reset for use with new batteries Yes
Battery voltage Yes
Ohmic value display Yes
Overcharge indicator Yes
Low battery / recharge indicator Yes
Extreme temperature indicator Yes

Physical Specifications

Dimensions 55mm x 55mm x 19mm (sensor)
Case material ABS Plastic (IEC 68-2-32)
Water resistance IPX-5
Mounting Surface mount (adhesive/mechanical)

* Sensor continues to operate down to -40C. LCD display loses function if temp below -15C.

Download the PDF →

BATTERY STATE OF HEALTH INDICATOR

Description Battery Failure Warning System for Engine Starting Batteries
Part Number BI-12V-Smart-400
Applications All 12V batteries used to power engine cranking systems: Diesel and Gas Generators, Trucks and other Vehicles

Operating Parameters

System voltage, nominal 12V
Input voltage range 9 – 16V DC
Battery constructions supported Rechargeable VRLA, SLA, AGM, WET, MF
Battery types supported High rate, long life, general purpose batteries
Power consumption <15mAh (sensor)
Internal battery None
Operating temp -15C to 85C*
Battery size range 200 to 3000 CCA
Battery connection 8mm ‘Y’ for auto terminal
Communication connection RJ11, 2 conductor, 1m
Alarming Voltage Free, Dry Contact Closure/switch: Normally open: switch 5v-60v 100 mA continuous
Display LCD Red-light and LCD – Digital, graphical, icons
Buttons None
Test frequency Every engine cranking event
Test time ~3 sec.
Test technology Cranking Voltage Profile Analysis
Warranty 1 year
Reverse wiring protection Yes

Performance and Diagnostics

Replace battery indicator Yes
Automatic battery baseline calibration Yes
Cranking Health (CH) test Yes
Cranking State of Health (Csoh) analysis Yes
Automatic reset for use with new batteries Yes
Battery voltage Yes
Last Crank Performance Yes
Overcharge indicator Yes
Low battery / recharge indicator Yes
Extreme temperature indicator Yes

Physical Specifications

Dimensions 55mm x 55mm x 19mm (sensor)
Case material ABS Plastic (IEC 68-2-32)
Water resistance IPX-5
Mounting Surface mount (adhesive/mechanical)

* Sensor continues to operate down to -40C. LCD display loses function if temp below -15C.

Download the PDF →

BATTERY STATE OF HEALTH INDICATOR

Description Battery Failure Warning System for VRLA Batteries
Part Number BI-12V-Smart-500
Applications VRLA batteries for use in backup-power systems: UPS, telecom, renewable energy, industrial applications

Operating Parameters

System voltage, nominal 12V
Input voltage range 9 – 16V DC
Battery constructions supported Rechargeable VRLA, SLA, AGM
Battery types supported High rate, long life, general purpose batteries
Power consumption <4mAh (sensor)
Internal battery None
Operating temp -15C to 85C*
Battery size range 28 to 200 AH at the 8 hour rate
Battery connection 8mm ‘Y’ for auto terminal
Communication connection RJ11, 2 conductor, 30cm
Alarming Voltage Free, Dry Contact Closure/switch: Normally open: switch 12v-24v 100 mA continuous
Display LCD Red-light and LCD – Digital, graphical, icons
Buttons None
Test frequency Every minute
Test time ~0.03 sec.
Test technology Ohmic
Warranty 1 year
Reverse wiring protection Yes

Performance and Diagnostics

Replace battery indicator Yes
Automatic battery baseline developer and calibration Yes
State of Health (SOH) health test Yes
State of Health (SOH) health analysis Yes
Manual reset for use with new batteries Yes
Battery voltage Yes
Ohmic value display Yes
Overcharge indicator Yes
Low battery / recharge indicator Yes
Extreme temperature indicator Yes

Physical Specifications

Dimensions 55mm x 55mm x 19mm (sensor)
Case material ABS Plastic (IEC 68-2-32)
Water resistance IPX-5
Mounting Surface mount (adhesive/mechanical)

* Sensor continues to operate down to -40C. LCD display loses function if temp below -15C.